{"id":1767,"date":"2026-09-10T05:01:59","date_gmt":"2026-09-10T05:01:59","guid":{"rendered":"https:\/\/benlongkj.com\/?p=1767"},"modified":"2026-09-10T05:02:02","modified_gmt":"2026-09-10T05:02:02","slug":"measurement-and-measuring-instruments","status":"publish","type":"post","link":"https:\/\/benlongkj.com\/tr\/blog\/measurement-and-measuring-instruments\/","title":{"rendered":"Devre kesici test ekipmanlar\u0131 i\u00e7in \u00f6l\u00e7\u00fcm ve \u00f6l\u00e7me cihazlar\u0131n\u0131n detayl\u0131 a\u00e7\u0131klamas\u0131"},"content":{"rendered":"<p>Devre kesici \u00fcretiminin herhangi bir fabrika denetiminde, denet\u00e7i odak noktas\u0131n\u0131 kesicinin kendisinden, ayn\u0131 kesicinin test edilmesi s\u0131ras\u0131nda kullan\u0131lan ekipmana kayd\u0131rma e\u011filimindedir. \u0130lgili soru, test tezgah\u0131n\u0131n ne kadar g\u00fcvenilir oldu\u011fudur. 47,2 saniyelik bir s\u00fcre tek ba\u015f\u0131na anlams\u0131zd\u0131r. Bu \u00f6l\u00e7\u00fcm\u00fcn nereden geldi\u011fini ve hangi bulgularla ulusal saniye standard\u0131 ile kar\u015f\u0131la\u015ft\u0131r\u0131labilece\u011fini bilmek \u00f6nemlidir. Bu nedenle, her \u00f6l\u00e7\u00fcm\u00fcn dok\u00fcmantasyonla kan\u0131tlanabilece\u011fi bir \u00f6l\u00e7\u00fcm zinciri s\u00f6z konusudur.<\/p>\n<p>Bu, <strong>\u00f6l\u00e7\u00fcm ve \u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong>alan\u0131d\u0131r: MCB, MCCB, RCCB ve enerji sayac\u0131 \u00fcreticileri i\u00e7in bu, entelekt\u00fcel bir egzersizden \u00e7ok pratik bir uygulamad\u0131r. Ba\u015fka bir deyi\u015fle, bu t\u00fcr cihazlar\u0131n uygun dok\u00fcmantasyonla akredite bir laboratuvar taraf\u0131ndan kalibre edildi\u011fi varsay\u0131l\u0131r.<\/p>\n<p>Bu rehber, bir devre kesici test tezgah\u0131nda neyin \u00f6l\u00e7\u00fclmesi gerekti\u011fini, \u00f6l\u00e7\u00fcm zincirinin nas\u0131l anla\u015f\u0131laca\u011f\u0131n\u0131, akredite bir laboratuvardan kalibrasyon raporunun nas\u0131l okunaca\u011f\u0131n\u0131, test aral\u0131klar\u0131n\u0131n nas\u0131l tan\u0131mlanaca\u011f\u0131n\u0131 ve \u00f6l\u00e7\u00fcm yeteneklerinin ekipman \u00fcretilmeden \u00f6nce sat\u0131n alma s\u00f6zle\u015fmesine nas\u0131l dahil edilece\u011fini \u00f6zetlemektedir.<\/p>\n<h2>Bir Kesici Fabrikas\u0131nda \u00d6l\u00e7\u00fcm ve \u00d6l\u00e7\u00fcm Cihazlar\u0131n\u0131n Anlam\u0131<\/h2>\n<p>Teknik m\u00fchendislikte, <strong>\u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong> belirli bir \u00f6l\u00e7\u00fcm\u00fcn belirli de\u011ferlerini bulmak i\u00e7in kullan\u0131lan ara\u00e7lard\u0131r. \u00c7e\u015fitli d\u00fc\u015f\u00fck voltajl\u0131 elektrik cihazlar\u0131 \u00fcreten bir fabrikada, genellikle her gerekli \u00f6l\u00e7\u00fcm ya \u00e7ok b\u00fcy\u00fck, \u00e7ok k\u00fc\u00e7\u00fck ya da k\u0131sa s\u00fcreli oldu\u011fundan \u00e7ok daha kesin ve karma\u015f\u0131k hale gelir.<\/p>\n<p>Devre kesici \u00fcretimi, \u00e7e\u015fitli s\u0131n\u0131flarda <strong>\u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong>:<\/p>\n<ul>\n<li>gerektiren be\u015f farkl\u0131 \u00f6l\u00e7\u00fcm t\u00fcr\u00fcn\u00fc i\u00e7erir. Ak\u0131m. Ev tipi MCB'lerde 6 A nominal ak\u0131mdan ba\u015flayarak anl\u0131k yakla\u015f\u0131mda 10 kA'ya kadar y\u00fckselir. Ak\u0131m, kalibre edilmi\u015f metreyi besleyen ak\u0131m trafolar\u0131, Rogowski bobinleri veya hassas \u015f\u00f6nt diren\u00e7ler arac\u0131l\u0131\u011f\u0131yla \u00f6l\u00e7\u00fcl\u00fcr.<br \/>\nZaman. Termal \u00e7al\u0131\u015fma s\u00fcreleri saniyelerden saatlere kadar de\u011fi\u015firken, manyetik \u00e7al\u0131\u015fma s\u00fcresi birka\u00e7 milisaniye i\u00e7inde \u00f6l\u00e7\u00fclmelidir. Zaman, bir kristal referansl\u0131 dijital zamanlay\u0131c\u0131 ve bir trip alg\u0131lama sens\u00f6r\u00fc ile \u00f6l\u00e7\u00fcl\u00fcr.<br \/>\nDiren\u00e7. Kontakt diren\u00e7 de\u011ferleri mikro ohm cinsinden Kelvin mikro ohm metreler ile \u00f6l\u00e7\u00fclmelidir. 100 mikro ohm \u00fczerindeki terminal direnci, kesiciye giren ak\u0131m\u0131 bozma e\u011filimindedir.<br \/>\nGerilim. \u0130zolasyon, 1500 V ile 2500 V aras\u0131nda de\u011fi\u015fen AC gerilimlerle artan testlere tabi tutulur ve ka\u00e7ak ak\u0131m de\u011ferleri ile birlikte \u00f6l\u00e7\u00fcl\u00fcr.<br \/>\nS\u0131cakl\u0131k. \u00c7evre alan\u0131n\u0131n s\u0131cakl\u0131\u011f\u0131 ve \u00f6l\u00e7\u00fcm s\u0131ras\u0131nda kontak s\u0131cakl\u0131\u011f\u0131.<\/li>\n<\/ul>\n<p>Her \u00f6l\u00e7\u00fcm s\u00fcreci t\u00fcr\u00fc, belirli bir \u00f6l\u00e7\u00fcm cihaz\u0131, belirli \u00f6zellik aral\u0131\u011f\u0131, sapma davran\u0131\u015f\u0131 ve hatta belirli kalibrasyon gereksinimi gerektirir. \u00d6l\u00e7\u00fcm cihaz\u0131n\u0131n tek bir kalibrasyon ko\u015fulu yoktur, ancak \u00f6l\u00e7\u00fcm noktalar\u0131n\u0131n say\u0131s\u0131 kadar kalibrasyon ko\u015fulu vard\u0131r, bu da herhangi bir denet\u00e7inin bunlardan herhangi biri hakk\u0131nda radikal sorular sormas\u0131 i\u00e7in bir f\u0131rsat yarat\u0131r.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-1768\" src=\"https:\/\/benlongkj.com\/wp-content\/uploads\/2026\/09\/Calibration-Traceability-in-Breaker-Testing.webp\" alt=\"\" width=\"1448\" height=\"1086\" \/><\/p>\n<h2>Test Tezgah\u0131 Kendisi Bir \u00d6l\u00e7\u00fcm Cihaz\u0131d\u0131r<\/h2>\n<p>\u00c7o\u011fu \u00fcretim y\u00f6neticisinin d\u00fcnyay\u0131 g\u00f6rme \u015feklindeki \u00f6nemli de\u011fi\u015fiklik, termal kalibrasyon tezgahlar\u0131n\u0131n \u00fcretim ekipman\u0131 olarak g\u00f6r\u00fclmesi ve \u00fcretim ekipman\u0131 gibi muamele g\u00f6rmesidir. Maliyetleri \u00fcretim ara\u00e7lar\u0131 gibi tahmin edilir ve bak\u0131mlar\u0131 da \u00fcretim ekipman\u0131 gibi yap\u0131l\u0131r. Ancak, asl\u0131nda, bunlar <strong>\u00f6l\u00e7\u00fcm ve \u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong>, kategorisine girer, \u00e7\u00fcnk\u00fc fiziksel \u00e7\u0131kt\u0131 \u00fcreten \u00fcretim ekipmanlar\u0131n\u0131n aksine, bir termal kalibrasyon tezgah\u0131 sadece bir say\u0131 \u00fcretir ve b\u00f6ylece bir kalite spesifikasyonu sa\u011flar.<\/p>\n<p>Sonu\u00e7 olarak, test \u00f6l\u00e7erlerden gelen gereksinimler, tan\u0131mlama, kalibrasyon durumu i\u015faretlemesi, belirlenmi\u015f aral\u0131klar, ba\u015flang\u0131\u00e7 ve biti\u015f verileri, tolerans ihlalleri ve \u00e7evre kontrol\u00fc gibi 500 A kalibrasyon tezgahlar\u0131 i\u00e7in ge\u00e7erlidir. Bizim rehberimiz <a href=\"https:\/\/benlongkj.com\/tr\/blog\/what-is-an-mcb-testing-laboratory\/\">bir MCB test laboratuvar\u0131n\u0131n asl\u0131nda neler i\u00e7erdi\u011fi<\/a> bu gereksinimlerin test alan\u0131n\u0131n fiziksel d\u00fczenini nas\u0131l \u015fekillendirdi\u011fini anlat\u0131r.<\/p>\n<p>Bir ge\u00e7\/kal test cihaz\u0131 ile bir \u00f6l\u00e7\u00fcm cihaz\u0131 aras\u0131ndaki fark da burada \u00f6nemlidir. Bir ge\u00e7\/kalm test cihaz\u0131 sadece okumalar\u0131n sabit s\u0131n\u0131rlar i\u00e7inde olup olmad\u0131\u011f\u0131n\u0131 kontrol ederken, bir kalibrasyon tezgah\u0131 baz\u0131 parametreleri \u00f6l\u00e7er ve b\u00f6ylece kullan\u0131c\u0131ya sa\u011flanan verilerle ilgili sorumluluklar verir. Teknik rehberimiz <a href=\"https:\/\/benlongkj.com\/tr\/blog\/mccb-calibration-machine-tips-for-optimal-performance\/\">MCCB kalibrasyon makinesi se\u00e7imi<\/a> bu s\u0131n\u0131r\u0131n pratikte nerede oldu\u011funu kapsar.<\/p>\n<h2>\u00d6l\u00e7\u00fcm \u0130zlenebilirli\u011fi: Zincir A\u00e7\u0131klamas\u0131<\/h2>\n<p><strong>\u00d6l\u00e7\u00fcm izlenebilirli\u011fi<\/strong> belirli bir \u00f6l\u00e7\u00fcm\u00fcn, s\u00fcrekli bir kalibrasyon zinciri arac\u0131l\u0131\u011f\u0131yla birincil bir referansa ba\u011flanabilece\u011fini tan\u0131mlamak i\u00e7in kullan\u0131lan bir terimdir (zincirin her halkas\u0131 belirli bir \u00f6l\u00e7\u00fcm belirsizli\u011fini garanti eder).<br \/>\nBir devre kesici \u00fcreticisi durumunda, bu zincir d\u00f6rt halkadan olu\u015fur.<\/p>\n<ol>\n<li>\u2460. halka: SI tan\u0131m\u0131. Amper ve saniyenin tan\u0131m\u0131 fiziksel sabitlere dayan\u0131r ve ulusal metroloji enstit\u00fcleri taraf\u0131ndan uygulan\u0131r.\n<p>\u2461. halka ulusal metroloji kurumu. NIST (ABD), PTB (Almanya), NPL (\u0130ngiltere), NIM (\u00c7in). Bu kurumlar birincil standartlar\u0131 korur ve akredite laboratuvarlar\u0131n \u00e7al\u0131\u015fma standartlar\u0131n\u0131n kalibrasyonlar\u0131n\u0131 yapar.<\/p>\n<p>\u2462. halka ISO\/IEC 17025 akreditasyonu alm\u0131\u015f, referans standartlar\u0131 ulusal enstit\u00fcye kar\u015f\u0131 kalibre eden ve fabrika taraf\u0131ndan saklanan sertifikalar\u0131 veren akredite \u00fc\u00e7\u00fcnc\u00fc taraf kalibrasyon laboratuvar\u0131d\u0131r.<\/p>\n<p>\u2463. halka, bu referans standartlara dayal\u0131 olarak belirli aral\u0131klarla kalibre edilen (yerinde veya kalibrasyon i\u00e7in g\u00f6nderilen) test tezgah\u0131d\u0131r.<\/li>\n<\/ol>\n<p>Bu zincirin herhangi bir ba\u011flant\u0131s\u0131n\u0131 \u00e7\u0131kar\u0131n ve zincir de\u011fersiz hale gelir. Akreditasyonu olmayan veya ba\u015fka parametreler i\u00e7in akredite edilmi\u015f bir laboratuvardan al\u0131nan kalibrasyon sertifikas\u0131, izlenebilirlik kan\u0131t\u0131 olarak hizmet veremez.<\/p>\n<h3>Akreditasyon kapsam\u0131, al\u0131c\u0131lar\u0131n \u00e7ok s\u0131k g\u00f6z ard\u0131 etti\u011fi konudur<\/h3>\n<p>Akreditasyon, laboratuvar\/\u015firket baz\u0131nda de\u011fil, \u00f6l\u00e7\u00fcm parametresi ve aral\u0131\u011f\u0131 baz\u0131nda \u00e7al\u0131\u015f\u0131r. 100 A DC ak\u0131m\u0131 i\u00e7in akredite edilmi\u015f bir laboratuvar, laboratuvar size sertifika vermek istese bile 2000 A AC ak\u0131m kayna\u011f\u0131n\u0131 sertifikaland\u0131ramaz.<\/p>\n<h2>\u00dc\u00e7\u00fcnc\u00fc Taraf Kalibrasyon Raporu Okuma<\/h2>\n<p>Uygun bir kalibrasyon raporu, tan\u0131mlanm\u0131\u015f bir dizi \u00f6\u011fe i\u00e7erir. Orada ne olmas\u0131 gerekti\u011fini bilmek, eksik olan\u0131 g\u00f6rmeyi kolayla\u015ft\u0131r\u0131r.<\/p>\n<table>\n<tbody>\n<tr>\n<td>\u00d6\u011feler<\/td>\n<td>Ne yazmas\u0131 gerekir<\/td>\n<td>Neden \u00f6nemli?<\/td>\n<\/tr>\n<tr>\n<td>Laboratuvar tan\u0131mlamas\u0131<\/td>\n<td>\u0130sim, adres, akreditasyon kurumu, akreditasyon numaras\u0131<\/td>\n<td>Bir denet\u00e7inin akreditasyonu ba\u011f\u0131ms\u0131z olarak do\u011frulamas\u0131n\u0131 sa\u011flar<\/td>\n<\/tr>\n<tr>\n<td>\u00dcr\u00fcn tan\u0131mlamas\u0131<\/td>\n<td>Ekipman a\u00e7\u0131klamas\u0131, \u00fcretici, model, benzersiz seri veya varl\u0131k numaras\u0131<\/td>\n<td>Sertifikay\u0131 bir makineye ba\u011flar, makine tipine de\u011fil<\/td>\n<\/tr>\n<tr>\n<td>Kalibrasyon tarihi<\/td>\n<td>\u00d6l\u00e7\u00fcmlerin al\u0131nd\u0131\u011f\u0131 ger\u00e7ek tarih<\/td>\n<td>Kalibrasyon aral\u0131\u011f\u0131n\u0131n ba\u015flang\u0131\u00e7 noktas\u0131<\/td>\n<\/tr>\n<tr>\n<td>\u00c7evresel ko\u015fullar<\/td>\n<td>Kalibrasyon s\u0131ras\u0131nda ortam s\u0131cakl\u0131\u011f\u0131 ve ba\u011f\u0131l nem<\/td>\n<td>Sonu\u00e7lar yaln\u0131zca kar\u015f\u0131la\u015ft\u0131r\u0131labilir ko\u015fullar alt\u0131nda ge\u00e7erlidir<\/td>\n<\/tr>\n<tr>\n<td>Kullan\u0131lan referans standartlar<\/td>\n<td>Laboratuvar\u0131n kendi standartlar\u0131n\u0131n tan\u0131mlanmas\u0131 ve kalibrasyon durumu<\/td>\n<td>\u0130zlenebilirlik zincirindeki yukar\u0131 ak\u0131\u015f ba\u011flant\u0131s\u0131n\u0131 kan\u0131tlar<\/td>\n<\/tr>\n<tr>\n<td>Bulundu\u011fu haliyle veriler<\/td>\n<td>Herhangi bir ayar yap\u0131lmadan \u00f6nceki okumalar<\/td>\n<td>Ge\u00e7mi\u015f \u00fcretimin ge\u00e7erli olup olmad\u0131\u011f\u0131n\u0131 g\u00f6steren tek veri<\/td>\n<\/tr>\n<tr>\n<td>Ayar sonras\u0131 veriler<\/td>\n<td>Ayarlamadan sonraki okumalar<\/td>\n<td>Bir sonraki aral\u0131\u011f\u0131n ba\u015flang\u0131\u00e7 ko\u015fulunu belirler<\/td>\n<\/tr>\n<tr>\n<td>\u00d6l\u00e7\u00fcm belirsizli\u011fi<\/td>\n<td>Kapsama fakt\u00f6r\u00fc ve kapsama olas\u0131l\u0131\u011f\u0131 ile geni\u015fletilmi\u015f belirsizlik<\/td>\n<td>Olmadan, say\u0131lar tan\u0131ml\u0131 bir g\u00fcvene sahip de\u011fildir<\/td>\n<\/tr>\n<tr>\n<td>Karar kural\u0131<\/td>\n<td>Belirsizli\u011fin herhangi bir ge\u00e7me\/kalma ifadesinde nas\u0131l ele al\u0131nd\u0131\u011f\u0131<\/td>\n<td>Sertifika uygunluk belirtti\u011finde gereklidir<\/td>\n<\/tr>\n<tr>\n<td>Yetkilendirme<\/td>\n<td>\u0130mzal\u0131 yetkili veya e\u015fde\u011fer elektronik yetkilendirme<\/td>\n<td>Rapor i\u00e7in hesap verebilirli\u011fi sa\u011flar<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Bulundu\u011fu haliyle veriler, insanlar\u0131n g\u00f6z ard\u0131 etti\u011fi bilgidir<\/h3>\n<p>Bir\u00e7ok al\u0131c\u0131 sadece makinenin kalibre edildi\u011fini g\u00f6steren bir ka\u011f\u0131t ister. Laboratuvar \u00f6nce cihaz\u0131 kalibre edip sonra kullan\u0131rsa, ka\u011f\u0131t cihaz\u0131n ge\u00e7ti\u011fini s\u00f6yler ancak \u00f6nceki \u00fcretim ay\u0131 hakk\u0131nda hi\u00e7bir bilgi vermez. Kalibrasyon hizmeti i\u00e7in her zaman bulundu\u011fu haliyle ve ayar sonras\u0131 verileri yaz\u0131n. Ekstra maliyeti yoktur ve sonradan ke\u015ffedilen sapmaya kar\u015f\u0131 tek korumad\u0131r.<\/p>\n<h3>Belirsizlik \u00f6l\u00e7\u00fcm\u00fc, do\u011frulu\u011fa benzer de\u011fildir<\/h3>\n<p><strong>\u00d6l\u00e7\u00fcm belirsizli\u011fi<\/strong> elde edilen sonu\u00e7la ilgili \u015f\u00fcpheyi nicelendirir. Genellikle k = 2 ile geni\u015fletilmi\u015f belirsizlik olarak iletilir, bu da kesinlik anlam\u0131na gelir. E\u011fer 135.0 A \u00f6l\u00e7\u00fcm\u00fc ve k = 2 i\u00e7in 0.4 A geni\u015fletilmi\u015f belirsizli\u011fimiz varsa, ger\u00e7ek de\u011ferin b\u00fcy\u00fck olas\u0131l\u0131kla 134.6 A ile 135.4 A aras\u0131nda oldu\u011funu s\u00f6yleyebiliriz. Ancak do\u011fruluk, elde edilen de\u011ferin ne kadar yak\u0131n olmas\u0131 gerekti\u011fine dair bir \u015firket spesifikasyonudur. Biri \u00f6l\u00e7\u00fclen de\u011ferdir, di\u011feri ise bir beyan. Denetim sonu\u00e7lar\u0131 genellikle ilkini ikinci olarak kabul etmekten kaynaklan\u0131r.<\/p>\n<h2>Test Belirsizlik Oran\u0131: Referans\u0131n\u0131z\u0131n Tezgah\u0131n\u0131zdan Daha \u0130yi Olmas\u0131 Neden Gereklidir<\/h2>\n<p>End\u00fcstriyel metrolojide temel prensip, test belirsizlik oran\u0131n\u0131n 4:1 veya daha b\u00fcy\u00fck olmas\u0131d\u0131r, bu da referans standard\u0131n\u0131n kalibrasyon cihaz\u0131ndan d\u00f6rt kat daha do\u011fru olmas\u0131 gerekti\u011fi anlam\u0131na gelir. Bir\u00e7ok kalite sistemi ekonomik olarak m\u00fcmk\u00fcnse 10:1 oran\u0131n\u0131 tercih eder.<\/p>\n<p>Devre kesici testine uyguland\u0131\u011f\u0131nda, hesaplama somuttur. Benlong\u2019un <a href=\"https:\/\/benlongkj.com\/tr\/mcb-automatic-testing-line-product\/\">MCB otomatik test hatt\u0131<\/a> okuma do\u011frulu\u011funu art\u0131 veya eksi %0.5 ve anl\u0131k atma i\u00e7in zamanlama do\u011frulu\u011funu art\u0131 veya eksi 1 ms olarak belirtir. Bu ak\u0131m kanal\u0131n\u0131 4:1 oran\u0131nda kalibre etmek i\u00e7in \u00e7al\u0131\u015fma aral\u0131\u011f\u0131nda art\u0131 veya eksi %0.125\u2019ten daha iyi bir referans ampermetreye ihtiyac\u0131n\u0131z vard\u0131r. Bu zamanlama kanal\u0131n\u0131 kalibre etmek i\u00e7in art\u0131 veya eksi 0.25 ms\u2019den daha iyi bir zaman referans\u0131na ihtiyac\u0131n\u0131z vard\u0131r.<\/p>\n<p>Ayn\u0131 mant\u0131k enerji sayac\u0131 \u00e7al\u0131\u015fmalar\u0131n\u0131 da y\u00f6netir, burada oran do\u011frudan uygulamaya yaz\u0131l\u0131r: Bir S\u0131n\u0131f 0.2 saya\u00e7, S\u0131n\u0131f 0.05 referans standard\u0131na kar\u015f\u0131 do\u011frulan\u0131r, d\u00f6rt bir oran\u0131nda. K\u0131lavuzumuzdaki detayl\u0131 a\u00e7\u0131klama <a href=\"https:\/\/benlongkj.com\/tr\/news\/electric-meter-test\/\">elektrik sayac\u0131 test ekipman\u0131 ve do\u011fruluk do\u011frulamas\u0131<\/a> bu gereksinimin t\u00fcm tezgah mimarisini nas\u0131l y\u00f6nlendirdi\u011fini g\u00f6sterir.<\/p>\n<p><span style=\"color: #991b1b;\">Bir tedarik\u00e7i size b\u00f6lgenizdeki herhangi bir akredite laboratuvar\u0131n kalibre edebilece\u011finden daha s\u0131k\u0131 do\u011frulu\u011fa sahip bir tezgah teklif ederse, spesifikasyon dekoratiftir. \u0130mzalamadan \u00f6nce kalibrasyon uygunlu\u011funu do\u011frulay\u0131n.<\/span><\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-1769\" src=\"https:\/\/benlongkj.com\/wp-content\/uploads\/2026\/09\/MCB-Long-Time-Thermal-Calibration-Test-Report.webp\" alt=\"\" width=\"1448\" height=\"1086\" \/><\/p>\n<h2>Hangi Parametrelerin Kalibrasyona \u0130htiyac\u0131 Var ve Ne S\u0131kl\u0131kla<\/h2>\n<p>Her kanal ayn\u0131 riski ta\u015f\u0131maz ve kalibrasyon b\u00fct\u00e7eleri s\u0131n\u0131rl\u0131d\u0131r. A\u015fa\u011f\u0131daki tablo, d\u00fc\u015f\u00fck voltaj kesici test ekipman\u0131 i\u00e7in yayg\u0131n end\u00fcstriyel uygulamay\u0131 yans\u0131t\u0131r.<\/p>\n<table>\n<tbody>\n<tr>\n<td>Parametre<\/td>\n<td>Tipik cihaz<\/td>\n<td>Yayg\u0131n aral\u0131k<\/td>\n<td>Kalibre edilmezse risk<\/td>\n<\/tr>\n<tr>\n<td>Test ak\u0131m\u0131, d\u00fc\u015f\u00fck aral\u0131k<\/td>\n<td>Hassas \u015f\u00f6nt veya CT art\u0131 kalibre edilmi\u015f saya\u00e7<\/td>\n<td>12 ay<\/td>\n<td>Termal atma s\u00fcreleri sistematik olarak kayar; t\u00fcm partiler yanl\u0131\u015f kalibre edilir<\/td>\n<\/tr>\n<tr>\n<td>Test ak\u0131m\u0131, y\u00fcksek aral\u0131k<\/td>\n<td>Y\u00fcksek ak\u0131m \u015f\u00f6nt\u00fc veya Rogowski bobini<\/td>\n<td>12 ay<\/td>\n<td>Manyetik atma, nominal ak\u0131m\u0131n yanl\u0131\u015f kat\u0131nda do\u011frulan\u0131r<\/td>\n<\/tr>\n<tr>\n<td>Atma zamanlay\u0131c\u0131s\u0131, termal<\/td>\n<td>Dijital zamanlay\u0131c\u0131, kristal referansl\u0131<\/td>\n<td>12 ila 24 ay<\/td>\n<td>Atma pencereleri yanl\u0131\u015f uygulan\u0131r; yava\u015f kesicilerde yanl\u0131\u015f ge\u00e7i\u015f<\/td>\n<\/tr>\n<tr>\n<td>Atma zamanlay\u0131c\u0131s\u0131, anl\u0131k<\/td>\n<td>Y\u00fcksek \u00e7\u00f6z\u00fcn\u00fcrl\u00fckl\u00fc zamanlay\u0131c\u0131, milisaniye s\u0131n\u0131f\u0131<\/td>\n<td>12 ay<\/td>\n<td>K\u0131sa devre yan\u0131t\u0131 veri sayfas\u0131nda yanl\u0131\u015f beyan edilir<\/td>\n<\/tr>\n<tr>\n<td>Mikro-ohmmetre<\/td>\n<td>D\u00f6rt telli Kelvin k\u00f6pr\u00fcs\u00fc<\/td>\n<td>12 ay<\/td>\n<td>K\u00f6t\u00fc kaynaklar ve kirli kontaklar muayeneden ge\u00e7er<\/td>\n<\/tr>\n<tr>\n<td>Dielektrik test cihaz\u0131<\/td>\n<td>Y\u00fcksek voltaj kayna\u011f\u0131 ve ka\u00e7ak \u00f6l\u00e7er<\/td>\n<td>12 ay<\/td>\n<td>\u0130zolasyon kusurlar\u0131 ka\u00e7\u0131r\u0131l\u0131r; do\u011frudan g\u00fcvenlik riski<\/td>\n<\/tr>\n<tr>\n<td>Ortam s\u0131cakl\u0131\u011f\u0131 sens\u00f6r\u00fc<\/td>\n<td>Termokupl veya RTD ile verici<\/td>\n<td>12 ila 24 ay<\/td>\n<td>S\u0131cakl\u0131k kompanzasyonu yanl\u0131\u015f d\u00fczeltme uygular<\/td>\n<\/tr>\n<tr>\n<td>Evde tutulan referans standartlar<\/td>\n<td>Tezgah\u0131 kontrol etmek i\u00e7in kullan\u0131lan \u00e7al\u0131\u015fma standartlar\u0131<\/td>\n<td>12 ay, akredite laboratuvar<\/td>\n<td>Son kalibrasyondan bu yana yap\u0131lan her dahili kontrol ge\u00e7ersizdir<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Standart s\u00fcre on iki ayd\u0131r, ancak bu zaman diliminin belirlenmesi yerle\u015fik bir rutin yerine d\u00fc\u015f\u00fcnceli bir de\u011ferlendirme meselesi olmal\u0131d\u0131r. Cihaz aktif olarak kullan\u0131l\u0131yorsa, \u00f6nceki sertifikalar\u0131n\u0131n ge\u00e7mi\u015fi cihaz\u0131n izin verilen sapma s\u0131n\u0131r\u0131na yakla\u015ft\u0131\u011f\u0131n\u0131 g\u00f6steriyorsa, cihaz ta\u015f\u0131nd\u0131ysa veya tamir edildiyse ya da m\u00fc\u015fteri veya sertifikasyon yapan kurulu\u015fun talebi \u00fczerine bu s\u00fcre azalt\u0131lmal\u0131d\u0131r. Belgelendirilmi\u015f sapma verisi olmadan s\u00fcre uzat\u0131m\u0131 kabul edilemez.<\/p>\n<h2>Tolerans D\u0131\u015f\u0131nda Oldu\u011funda<\/h2>\n<p>Tezgah\u0131n \u201ctolerans d\u0131\u015f\u0131\u201d \u00f6l\u00e7\u00fcmler yapt\u0131\u011f\u0131 ke\u015ffedildi\u011finde, bu bir dok\u00fcmantasyon meselesi de\u011fil, \u00fcretimdeki kusurlard\u0131r, \u00e7\u00fcnk\u00fc her birim art\u0131k hatal\u0131 \u00f6l\u00e7\u00fcmler yapt\u0131\u011f\u0131 kabul edilen bir cihazla test edilmi\u015ftir.<\/p>\n<p>Verilmesi gereken yan\u0131t, ters izlenebilirlikte a\u015fa\u011f\u0131daki ad\u0131mlar\u0131n ger\u00e7ekle\u015ftirilmesidir:<\/p>\n<p>\u201cBulunan veri\u201d i\u00e7in hatan\u0131n b\u00fcy\u00fckl\u00fc\u011f\u00fcn\u00fc ve y\u00f6n\u00fcn\u00fc belirleyin.\u201d<br \/>\nKay\u0131tlar\u0131 kullanarak \u00f6nceki kalibrasyondan bu yana o kanal i\u00e7in \u00fcretilen farkl\u0131 partileri tan\u0131mlay\u0131n.<br \/>\nHata d\u00fczeltilerek sonu\u00e7lar\u0131n tatmin edici olup olmad\u0131\u011f\u0131n\u0131 yeniden hesaplay\u0131n.<br \/>\nSonraki ad\u0131m, sonu\u00e7lar d\u00fczeltildikten sonra gereksinimleri kar\u015f\u0131lamayan partiler i\u00e7in \u00f6nleyici tedbirler almakt\u0131r.<br \/>\nHangi sonu\u00e7lar\u0131 elde ederseniz edin, t\u00fcm hesaplamalar\u0131n\u0131z\u0131 ve kararlar\u0131n\u0131z\u0131 belgeleyin.<\/p>\n<p><span style=\"color: #800000;\">Bu, yaln\u0131zca t\u00fcm sonu\u00e7lar\u0131 kaydeden elektronik bir sistem oldu\u011funda m\u00fcmk\u00fcnd\u00fcr. Tezgah sadece \u201cge\u00e7ti\/kald\u0131\u201d \u00f6l\u00e7\u00fcmleri yap\u0131yorsa veya hi\u00e7 kay\u0131t tutmuyorsa, \u201ctolerans d\u0131\u015f\u0131\u201d durumu bir kabusa d\u00f6n\u00fc\u015f\u00fcr.<\/span><\/p>\n<h2>\u00c7evresel Etkiler<\/h2>\n<p>Kesicilerin test sonu\u00e7lar\u0131 \u00e7evresel ko\u015fullardan \u00f6zellikle etkilenir, \u00e7\u00fcnk\u00fc bimetal \u015feritler test ak\u0131m\u0131ndan kaynaklanan \u0131s\u0131 ile \u00e7evreden gelen \u0131s\u0131y\u0131 ay\u0131rt edemez.<\/p>\n<p>A\u00e7ma s\u00fcresi de\u011fi\u015fiklikleri, s\u0131cakl\u0131ktaki her bir derece Celsius de\u011fi\u015fim i\u00e7in %1-2 kadar olabilir. Bu nedenle, \u00f6rne\u011fin \u00f6\u011fleden sonra sabaha g\u00f6re 12 derece daha s\u0131caksa, \u00f6l\u00e7\u00fcm sadece s\u0131cakl\u0131ktan dolay\u0131 yanl\u0131\u015f olacakt\u0131r. E\u015fde\u011fer olmayan iki azaltma y\u00f6ntemi mevcuttur:<\/p>\n<ul>\n<li>\u00c7evrenin kontrol\u00fc. Kalibrasyon alan\u0131, sertifikasyon laboratuvarlar\u0131n\u0131n da kulland\u0131\u011f\u0131 y\u00f6ntem olan 25\u00b0C\u00b13\u00b0C s\u0131cakl\u0131kta test edilmelidir.<\/li>\n<li>Yaz\u0131l\u0131mda telafi. Ortam s\u0131cakl\u0131klar\u0131 ger\u00e7ek zamanl\u0131 olarak izlenir ve buna g\u00f6re ak\u0131m veya kabul aral\u0131\u011f\u0131 ayarlan\u0131r. <a href=\"https:\/\/benlongkj.com\/tr\/mccb-long-time-thermal-calibration-bench-product\/\">MCCB uzun s\u00fcreli termal kalibrasyon tezgah\u0131<\/a> Bu nedenle, her istasyon i\u00e7in a\u00e7ma s\u00fcresi, test ak\u0131m\u0131, ortam s\u0131cakl\u0131\u011f\u0131 ve ge\u00e7me\/kalmama durumu kaydedilir ve laboratuvar kalitesinde tekrarlanabilirlik gereken durumlarda iste\u011fe ba\u011fl\u0131 \u00e7evresel bir oda desteklenir.<\/li>\n<\/ul>\n<p>Hangi y\u00f6ntem kullan\u0131l\u0131rsa kullan\u0131ls\u0131n, s\u0131cakl\u0131k sens\u00f6r\u00fcn\u00fcn \u00f6l\u00e7\u00fcm s\u00fcrecine dahil edilmesi ve b\u00f6ylece ak\u0131m ile zamanlama kanallar\u0131yla ayn\u0131 kalibrasyonun yap\u0131lmas\u0131 gerekecektir. Kalibre edilmemi\u015f termokupllara dayal\u0131 telafi \u015femalar\u0131n\u0131n kullan\u0131m\u0131 sadece daha fazla hata \u00fcretecek ve hatay\u0131 ortadan kald\u0131rmayacakt\u0131r.<\/p>\n<h2>So\u011futma, s\u0131ralama ve tekrarlanabilirlik<\/h2>\n<p>Kesici \u00f6l\u00e7\u00fcmlerini bozan, cihaz sorunlar\u0131ndan farkl\u0131 iki ek etki vard\u0131r.<\/p>\n<p>Birincisi, kesme an\u0131nda bimetalde ortaya \u00e7\u0131kan art\u0131k \u0131s\u0131d\u0131r ve bu, ikinci termal olarak test edilen kesicinin daha h\u0131zl\u0131 kesmesini sa\u011flar. Bu etki, ilk testten sonra \u00fc\u00e7 ila d\u00f6rt dakika bekleyerek veya testler aras\u0131nda zorunlu so\u011futma yaparak \u00f6nlenebilir.<br \/>\n\u0130kinci etki ise terminal durumu ile ilgilidir. Terminaller oksitlenmi\u015f veya kirliyse, temas direnci olu\u015fur ve cihaz\u0131n terminallerinde voltaj d\u00fc\u015fer. Test \u00f6ncesi terminallerin temizlenmesi sadece temizlik de\u011fil; \u00f6l\u00e7\u00fcm s\u00fcrecinin bir par\u00e7as\u0131d\u0131r.<\/p>\n<p>Tekrarlanabilirlik varsay\u0131lmamal\u0131, belirlenmelidir. Test ama\u00e7lar\u0131 i\u00e7in, ayn\u0131 makinede on test yap\u0131larak ve test s\u00fcresinin standart sapmas\u0131 hesaplanarak g\u00fcvenilir sonu\u00e7lar elde edilebilir. Ortalama test s\u00fcresinin standart sapmas\u0131 %5\u2019ten az ise, s\u00fcre\u00e7 yetene\u011fi Cpk = 1,33 olarak kabul edilebilir.<\/p>\n<h2>Otomatik hat \u00fczerinde metroloji<\/h2>\n<p>Otomasyon, \u00f6l\u00e7\u00fcmlerin ekonomisini fark edilmeden de\u011fi\u015ftiriyor. Manuel y\u00f6ntemde teknisyen de\u011feri \u00f6l\u00e7er ve not al\u0131rken, otomatik s\u00fcre\u00e7te t\u00fcm \u00f6l\u00e7\u00fcmler bilgisayara kaydedilir ve \u00f6l\u00e7\u00fcm ekipman\u0131n\u0131n seri numaras\u0131yla ili\u015fkilendirilir. B\u00f6ylece fabrika, <strong>\u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong> s\u00fcrekli olarak do\u011fru i\u015fleyi\u015fi izleyebilir.<\/p>\n<p>Bu, manuel y\u00f6ntemin sa\u011flayamad\u0131\u011f\u0131 avantajlar sunar:<\/p>\n<p>Kalibrasyonlar aras\u0131ndaki sapma tespiti. Ortalama test s\u00fcresi grafi\u011fi olu\u015fturularak y\u0131ll\u0131k kalibrasyondan \u00e7ok \u00f6nce herhangi bir cihaz sapmas\u0131 bulunabilir.<br \/>\n\u0130stasyonlar aras\u0131 kar\u015f\u0131la\u015ft\u0131rma. \u00c7ok istasyonlu s\u00fcre\u00e7te, bir istasyonun di\u011ferlerinden farkl\u0131 ve tutarl\u0131 \u00f6l\u00e7\u00fcmleri varsa, \u00fcr\u00fcn de\u011fil istasyonla ilgili bir sorun oldu\u011fu sonucuna var\u0131labilir.<br \/>\nDenetime haz\u0131r veri ihrac\u0131. Test verileri CSV, SQL veya MES format\u0131nda d\u0131\u015fa aktar\u0131labilir ve denetim s\u00fcrecinin verimlili\u011fi art\u0131r\u0131l\u0131r.<br \/>\n\u0130statistiksel s\u00fcre\u00e7 kontrol\u00fc. Kontrol grafikleri sadece nihai test sonu\u00e7lar\u0131n\u0131 de\u011fil, ayn\u0131 zamanda kaynak veya montajdaki s\u00fcre\u00e7leri de izlemeye olanak tan\u0131r.<\/p>\n<p>Teknik k\u0131lavuzumuzdaki istasyon baz\u0131nda ayr\u0131nt\u0131l\u0131 a\u00e7\u0131klama <a href=\"https:\/\/benlongkj.com\/tr\/news\/what-is-an-mcb-automatic-testing-line-a-complete-technical-guide\/\">bir MCB otomatik test hatt\u0131n\u0131n nas\u0131l \u00e7al\u0131\u015ft\u0131\u011f\u0131n\u0131<\/a> ak\u0131\u015f boyunca her \u00f6l\u00e7\u00fcm\u00fcn nerede yap\u0131ld\u0131\u011f\u0131n\u0131 g\u00f6sterir. Tam otomasyona hen\u00fcz haz\u0131r olmayan \u00fcreticiler i\u00e7in, <a href=\"https:\/\/benlongkj.com\/tr\/mcb-semi-automatic-thermal-trip-calibration-bench-type-a-product\/\">yar\u0131 otomatik termal atma kalibrasyon tezgah\u0131<\/a> operat\u00f6r zamanlama hatas\u0131n\u0131 ortadan kald\u0131ran bir.<\/p>\n<h2>ekipman sat\u0131n al\u0131rken \u00f6l\u00e7\u00fcm yetene\u011finin belirlenmesi<\/h2>\n<p>\u00c7o\u011fu \u00f6l\u00e7\u00fcm problemi, sat\u0131n alma sipari\u015fi a\u015famas\u0131nda, spesifikasyonun verim ve mekanik kapasiteyi ayr\u0131nt\u0131l\u0131 olarak tan\u0131mlay\u0131p do\u011frulu\u011fu tek bir kalem olarak ele ald\u0131\u011f\u0131 zaman yarat\u0131l\u0131r. Bir denetimden ge\u00e7ecek bir spesifikasyon a\u00e7\u0131k\u00e7a <strong>\u00f6l\u00e7\u00fcm ve \u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong> belirtir.<\/p>\n<h3>Anla\u015fma yapmadan \u00f6nce sa\u011flay\u0131c\u0131ya sorulacak sorular<\/h3>\n<ul>\n<li>Her bir \u00f6l\u00e7\u00fcm kanal\u0131n\u0131n belirtilen do\u011fruluk seviyesi nedir: \u00f6l\u00e7e\u011fin maksimumunun bir y\u00fczdesi mi yoksa son okuman\u0131n bir y\u00fczdesi mi? D\u00fc\u015f\u00fck de\u011ferlerde fark \u00f6nemlidir.<br \/>\nDo\u011fruluk aral\u0131\u011f\u0131 nedir? Maksimumun y\u00fczde biri do\u011frulu\u011fa sahip bir cihaz, d\u00fc\u015f\u00fck ak\u0131m \u00f6l\u00e7\u00fcmlerinde \u00e7ok daha k\u00f6t\u00fc \u00e7al\u0131\u015fabilir.<br \/>\nT\u00fcm servis vardiyas\u0131 boyunca s\u00fcr\u00fcklenme ve stabilite parametreleri nelerdir, tek bir \u00f6l\u00e7\u00fcmde de\u011fil?<br \/>\nCihaz\u0131n ana bile\u015fenleri nelerdir ve bunlar\u0131 ba\u011f\u0131ms\u0131z olarak de\u011fi\u015ftirmek ve kalibre etmek m\u00fcmk\u00fcn m\u00fcd\u00fcr?<br \/>\nKalibrasyon i\u00e7in \u00fc\u00e7\u00fcnc\u00fc taraf bir standart kullanmak m\u00fcmk\u00fcn m\u00fcd\u00fcr, yoksa cihaz ba\u015fka bir yere g\u00f6nderilmek zorunda m\u0131d\u0131r?<br \/>\nSat\u0131n alma sonras\u0131 \u00f6l\u00e7\u00fcmlerin nas\u0131l yap\u0131ld\u0131\u011f\u0131n\u0131 g\u00f6steren bir kalibrasyon sertifikas\u0131 veriliyor mu?<br \/>\nFAT ve SAT hangi testleri i\u00e7erir ve bunlar\u0131n herhangi biri standart kullanarak kanallar\u0131 kontrol eder mi?<br \/>\n\u00dcnitenin \u00fcretti\u011fi \u00e7\u0131kt\u0131 t\u00fcr\u00fc nedir ve baz\u0131 veriler kaydediliyor mu yoksa sadece sonu\u00e7lar m\u0131 g\u00f6steriliyor?<\/p>\n<p>Ayr\u0131ca, IEC 60898-1 veya IEC 60947-2 ile uyumluluk kar\u015f\u0131la\u015ft\u0131rma tablosu sa\u011flay\u0131n; hangi testlerin tamamland\u0131\u011f\u0131n\u0131 ve \u00fcnitenin spesifikasyonlara g\u00f6re nas\u0131l \u00e7al\u0131\u015ft\u0131\u011f\u0131n\u0131 g\u00f6sterir. B\u00f6yle bir belge sa\u011flayabilenler i\u00e7in, tedarik\u00e7i taraf\u0131ndan \u00e7ok \u015fey yap\u0131lm\u0131\u015f demektir.<\/li>\n<\/ul>\n<h2>\u00d6l\u00e7\u00fcm cihazlar\u0131n\u0131n y\u00f6netiminde yayg\u0131n hatalar<\/h2>\n<ul>\n<li>Referans kalibre edilmeden \u00f6l\u00e7\u00fcm masas\u0131 kalibre edilir. \u015eirket bak\u0131m s\u00fcrecinin bir par\u00e7as\u0131 olan ve ara kontrol i\u00e7in kullan\u0131lan \u00e7al\u0131\u015fma standard\u0131n\u0131n da akreditasyonu gerekir.<br \/>\nSertifikan\u0131n kapsam\u0131 dikkate al\u0131nmadan al\u0131nmas\u0131. Laboratuvar, sadece akredite olmakla kalmay\u0131p, kapsam ve parametre i\u00e7in akredite olmal\u0131d\u0131r.<br \/>\nBelirsizlikler s\u0131n\u0131rlar\u0131na yak\u0131n oldu\u011funda g\u00f6z ard\u0131 edilmesi. Toleranslar i\u00e7inde olan ancak belirsizli\u011fi s\u0131n\u0131r\u0131 a\u015fan okuma ge\u00e7erli say\u0131lmaz. Kurallar bu durumlar\u0131n nas\u0131l ele al\u0131naca\u011f\u0131n\u0131 belirtir.<br \/>\nBulunan verilerin dikkate al\u0131nmamas\u0131. Daha \u00f6nce bahsedilen bu hata listedeki en maliyetli hatad\u0131r.<br \/>\nAparatlar\u0131 mekanik de\u011fil, metrologik olarak ele almak. \u00d6l\u00e7\u00fcm s\u00fcrecinde bara, kelep\u00e7e ve kontaklar bulunur ve bunlar\u0131n direnci sonucu etkiler.<br \/>\nAral\u0131klar\u0131 unutmak. S\u00fcresi dolmu\u015f sertifika, cihaz normal \u00e7al\u0131\u015fsa bile iki ayl\u0131k \u00fcretimin ge\u00e7erli olmad\u0131\u011f\u0131 anlam\u0131na gelir.<br \/>\nSertifikalar\u0131 indekslemeden saklamak. Denetim s\u0131ras\u0131nda sunulamayan sertifika, hi\u00e7 verilmemi\u015f olanla e\u015fde\u011ferdir.<\/li>\n<\/ul>\n<h2>Bunun Maliyeti ve Sa\u011flad\u0131\u011f\u0131 De\u011fer<\/h2>\n<p>\u00c7ok kanall\u0131 kesici test tezgah\u0131n\u0131n akredite kalibrasyonunun y\u0131ll\u0131k maliyeti, ekipman\u0131n sermaye maliyeti ile kar\u015f\u0131la\u015ft\u0131r\u0131ld\u0131\u011f\u0131nda \u00f6nemsizdir ve k\u00f6t\u00fc bir denetim nedeniyle ortaya \u00e7\u0131kabilecek masraftan \u00e7ok daha k\u00fc\u00e7\u00fckt\u00fcr: \u00fcr\u00fcn lansman\u0131n\u0131 geciktiren ba\u015far\u0131s\u0131z bir sertifikasyon, teslimat anla\u015fmas\u0131n\u0131n iptaline yol a\u00e7an bir distrib\u00fct\u00f6r denetimi, ge\u00e7erli bir test kayd\u0131n\u0131n olmamas\u0131ndan kaynaklanan saha ar\u0131zas\u0131 ara\u015ft\u0131rmas\u0131 veya standartlardan sapmalar\u0131n tespit edilmemesi nedeniyle yap\u0131lan bir geri \u00e7a\u011f\u0131rma.<\/p>\n<p>Bu ticari arg\u00fcman, teknik arg\u00fcmandan daha az karma\u015f\u0131kt\u0131r. D\u00fczenlenmi\u015f ihracat pazarlar\u0131nda \u00fcr\u00fcnlerini satan herhangi bir \u00fcretici, sadece donan\u0131m de\u011fil, ayn\u0131 zamanda iyi belgelenmi\u015f uyumluluk da satar. <strong>\u00f6l\u00e7\u00fcm cihazlar\u0131n\u0131n kalibrasyonu<\/strong> uyumlulu\u011fun var oldu\u011funu garanti eden \u015feydir. Hindistan, T\u00fcrkiye, Brezilya ve K\u00f6rfez \u00fclkeleri gibi \u00fclkelerden m\u00fc\u015fteriler, tedarik\u00e7ileri nitelendirirken art\u0131k sadece \u00fcr\u00fcn sertifikalar\u0131na sahip olmak yerine test ekipmanlar\u0131n\u0131n kalibrasyon durumu hakk\u0131nda sorular sormaktad\u0131r. Bir \u00fcretici kalibrasyon durumu hakk\u0131nda soruya hemen cevap vermeye haz\u0131rsa, nitelendirme daha az zaman alabilir, \u00e7\u00fcnk\u00fc m\u00fc\u015fteri itirazlar\u0131 nitelendirme a\u015famas\u0131nda ortaya \u00e7\u0131kmaz.<\/p>\n<h2>Benlong Otomasyon ve \u00d6l\u00e7\u00fcm S\u0131n\u0131f\u0131 Test Ekipmanlar\u0131<\/h2>\n<p><a href=\"https:\/\/benlongkj.com\/tr\/\">Benlong Otomasyon Teknoloji Ltd. \u015eti.<\/a> 2008 y\u0131l\u0131nda \u00c7in'in d\u00fc\u015f\u00fck voltajl\u0131 elektrik end\u00fcstrisinin merkezi olan Zhejiang Eyaleti, Wenzhou'da kurulan, d\u00fc\u015f\u00fck voltajl\u0131 elektrik \u00fcreticileri i\u00e7in otomasyon sistemleri ve test cihazlar\u0131 tasarlayan ve \u00fcreten bir firmad\u0131r. \u015eirket, termal kalibrasyon raflar\u0131, manyetik a\u00e7ma test raflar\u0131, dielektrik test ekipmanlar\u0131, dayan\u0131kl\u0131l\u0131k test raflar\u0131, enerji sayac\u0131 kalibrasyon ekipmanlar\u0131 ve bilgisayar kontroll\u00fc test kompleksleri tasarlamaktad\u0131r.<\/p>\n<p>Bu cihazlar \u00fcretim ekipmanlar\u0131 gibi \u00f6l\u00e7\u00fcm ekipmanlar\u0131 oldu\u011fundan, her biri belirtilen kanal ba\u015f\u0131na do\u011fruluk, \u00e7al\u0131\u015fma g\u00fcn\u00fc ba\u015f\u0131na stabilite de\u011ferleri, gelecekte referans i\u00e7in veri kayd\u0131 ve MES ba\u011flant\u0131s\u0131 uyumunda tasarlanm\u0131\u015ft\u0131r. Bu nedenle, t\u00fcm ekipman kalibrasyon sertifikalar\u0131 ile birlikte sa\u011flanmakta ve cihaz\u0131n tam \u00fcretime ge\u00e7meden \u00f6nce test edildi\u011finden emin olmak i\u00e7in FAT ve SAT kabul testlerinden ge\u00e7mektedir.<\/p>\n<p>\u00dcreticiler ekipmanlar\u0131 \u00fczerinde \u00e7al\u0131\u015fmaya ba\u015flamadan \u00f6nce neyi \u00f6l\u00e7t\u00fcklerini, hangi do\u011frulu\u011fu talep ettiklerini ve neyi kan\u0131tlayabileceklerini anlamal\u0131d\u0131r. Benlong m\u00fchendisleri \u00e7al\u0131\u015fmalar\u0131na bu analizden ba\u015flar.<\/p>\n<h2>Kaynak\u00e7a<\/h2>\n<ul>\n<li><a href=\"https:\/\/www.iso.org\/standard\/66912.html\" target=\"_blank\" rel=\"noopener\">ISO\/IEC 17025:2017 \u2014 Test ve Kalibrasyon Laboratuvarlar\u0131n\u0131n Yeterlili\u011fi i\u00e7in Genel Gereksinimler<\/a>. \u00dc\u00e7\u00fcnc\u00fc taraf kalibrasyon laboratuvar\u0131n\u0131n neyi g\u00f6stermesi gerekti\u011fini ve raporlar\u0131n\u0131n neleri i\u00e7ermesi gerekti\u011fini tan\u0131mlayan akreditasyon standard\u0131.<\/li>\n<li><a href=\"https:\/\/ilac.org\/publications-and-resources\/ilac-policy-series\/\" target=\"_blank\" rel=\"noopener\">ILAC Politika Serisi \u2014 ILAC P14, Kalibrasyonda \u00d6l\u00e7\u00fcm Belirsizli\u011fi Politikas\u0131<\/a>. Akredite kalibrasyon sertifikalar\u0131nda geni\u015fletilmi\u015f belirsizli\u011fin tahmin edilmesi ve belirtilmesi i\u00e7in gereksinimleri belirler.<\/li>\n<li><a href=\"https:\/\/www.bipm.org\/en\/committees\/jc\/jcgm\/publications\" target=\"_blank\" rel=\"noopener\">JCGM Yay\u0131nlar\u0131 (BIPM) \u2014 \u00d6l\u00e7\u00fcm Belirsizli\u011finin \u0130fadesi Rehberi (GUM) ve Uluslararas\u0131 Metroloji S\u00f6zl\u00fc\u011f\u00fc (VIM)<\/a>. Her belirsizlik b\u00fct\u00e7esinin ve her izlenebilirlik tan\u0131m\u0131n\u0131n arkas\u0131ndaki iki temel belge.<\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66277\" target=\"_blank\" rel=\"noopener\">IEC 60947-2 \u2014 D\u00fc\u015f\u00fck gerilim anahtarlama ve kontrol cihazlar\u0131, B\u00f6l\u00fcm 2: Devre kesiciler<\/a>. MCCB test tezgahlar\u0131n\u0131n yeniden \u00fcretebilmesi gereken a\u015f\u0131r\u0131 y\u00fck, k\u0131sa devre ve rutin test gereksinimlerini tan\u0131mlar.<\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/66269\" target=\"_blank\" rel=\"noopener\">IEC 60898-1 \u2014 Ev ve benzeri tesisatlar i\u00e7in a\u015f\u0131r\u0131 ak\u0131m korumal\u0131 devre kesiciler<\/a>. MCB kalibrasyon ekipmanlar\u0131n\u0131n olu\u015fturmas\u0131 ve \u00f6l\u00e7mesi gereken a\u00e7ma zaman\u0131 pencereleri ve test ko\u015fullar\u0131n\u0131 belirtir.<\/li>\n<\/ul>\n<p>Bir fabrikadan \u00e7\u0131kan bir kesici, ar\u0131za ko\u015fullar\u0131 alt\u0131nda nas\u0131l davranaca\u011f\u0131na dair \u00f6rt\u00fcl\u00fc bir vaat ta\u015f\u0131r. Bu vaadin arkas\u0131ndaki tek kan\u0131t, bir makine taraf\u0131ndan \u00fcretilen bir dizi say\u0131d\u0131r ve bu say\u0131lar, arkas\u0131ndaki izlenebilirlik kadar de\u011ferlidir. <strong>\u00f6l\u00e7\u00fcm ve \u00f6l\u00e7\u00fcm cihazlar\u0131<\/strong> test sonu\u00e7lar\u0131n\u0131 kan\u0131ta d\u00f6n\u00fc\u015ft\u00fcren, akredite kalibrasyon, belgelenmi\u015f belirsizlik, kontroll\u00fc \u00e7evresel ko\u015fullar ve birim ba\u015f\u0131na veri kayd\u0131 ile y\u00f6netilen bir sistem olarak ele almakt\u0131r. Ayr\u0131ca, uluslararas\u0131 al\u0131c\u0131lar\u0131n giderek ilk kontrol etti\u011fi \u015fey budur.<\/p>","protected":false},"excerpt":{"rendered":"<p>At any factory audit of circuit breaker manufacturing, the auditor tends to shift the focus from the breaker itself to the equipment that has been used during the testing of the same breaker. The relevant question is how trustworthy the bench is. A time of 47.2 seconds is meaningless on its own. It is important [&hellip;]<\/p>\n","protected":false},"author":3,"featured_media":1770,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[],"class_list":["post-1767","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"blocksy_meta":[],"acf":[],"_links":{"self":[{"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/posts\/1767","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/users\/3"}],"replies":[{"embeddable":true,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/comments?post=1767"}],"version-history":[{"count":1,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/posts\/1767\/revisions"}],"predecessor-version":[{"id":1771,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/posts\/1767\/revisions\/1771"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/media\/1770"}],"wp:attachment":[{"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/media?parent=1767"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/categories?post=1767"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/benlongkj.com\/tr\/wp-json\/wp\/v2\/tags?post=1767"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}